How is the current-carrying capacity of switchgear busbars calculated?

开关柜母排载流量怎么算?三步:电流计算(柜内总电流)→截面选型(按载流量表选铜排留裕量20%~30%)→温升校验(≤70K防过热)。环境温度/多片并列降容修正,短路动热稳定校核,按GB/T 7251核算。

How to calculate current-carrying capacity of switchgear busbars

Current-Carrying Capacity Calculation: A Three-Step Verification Process

Calculating the current-carrying capacity of switchgear busbars (specifically copper bars) involves a three-step verification process: current calculation, cross-section selection, and temperature rise verification. Industry experts note that the calculation follows a specific workflow: determining the current (based on load capacity or total cabinet current), selecting the cross-section (choosing the copper bar size based on capacity while allowing for a safety margin), and verifying the temperature rise (ensuring it stays within permissible limits).
Busbar capacity is calculated in accordance with the GB/T 7251 standard and relevant copper bar capacity tables, with cross-section and temperature rise being the critical factors.

Three-Step Verification

  • Current Calculation: Total cabinet current (incomer current or aggregated load);
    serves as the basis for calculation;
  • Cross-section Selection: Copper bar cross-section (referencing capacity tables—e.g., a 60×6mm copper bar is rated for approx. 1000A); include a safety margin during selection;
  • Temperature Rise Verification: Check against permissible temperature rise limits (≤70K for copper bars) to prevent overheating;
  • Derating Adjustments: Adjustments for ambient temperature (derating if >40°C) and parallel busbar arrangements (derating factor);
  • Dynamic and Thermal Stability: Verification of short-circuit dynamic and thermal stability for the busbars to ensure safety.

Key Calculation Points

First, allow for a safety margin.
Include a margin in the current-carrying capacity (accounting for 20%–30% load growth) to prevent overloading. Second, verify temperature rise.
Ensure the temperature rise remains within permissible limits to prevent overheating and thermal aging.
Third, apply derating adjustments.
Adjust for ambient temperature and parallel arrangements to determine the actual current-carrying capacity accurately.
Fourth, perform short-circuit stability verification.

Dynamic and thermal stability under short-circuit conditions (resistance to deformation under high current) and safety verification.

Pitfalls to Avoid

First: “Undersized cross-section.”
An undersized cross-section leads to overheating; ensure adequate design margins.
Second: “Excessive temperature rise.”
Excessive temperature rise causes insulation aging; perform verification and adjustments.
Third: “Lack of short-circuit verification.”
Failure to verify short-circuit performance risks deformation;
ensure dynamic and thermal stability.

Trends and Recommendations

Busbars are trending toward “high current-carrying capacity,” specifically utilizing shaped copper bars (for optimized heat dissipation) and fully insulated busbars (for enhanced safety).
Designers are advised to follow a “three-step calculation” approach: incorporate design margins and verify temperature rise.
Accurate busbar calculations ensure stable heat dissipation within the cabinet.